Evaluation of the Computer Fire Model DETACT-QS - First edition 2022 - 1 recurso en línea (XXVI, 157 páginas) 50 ilustraciones - The Society of Fire Protection Engineers Series 2731-3646 .

Introduction -- Model Description -- Scenarios for Which Evaluation Is Sought -- Theoretical Basis for the Model -- Mathematical and Numerical Robustness -- Model Sensitivity -- Model Inputs0 -- Model Evaluation -- Summary of Analysis0 -- Limitations/User Guidelines -- Appendix A -- Appendix B.

This engineering practice Guide, based on the DETACT-QS program, describes a model for predicting the response time of ceiling-mounted heat detectors/sprinklers and smoke detectors, installed under large unobstructed ceilings, for fires with user-defined, time-dependent heat release rate curves. The Guide provides information on the technical features, theoretical basis, assumptions, limitations, and sensitivities as well as guidance on the use of DETACT-QS. Evaluation is based on comparing predictions from DETACT-QS with results from full-scale fire experiments conducted in compartments with ceiling heights ranging from 2.44 m (8 ft) to 12.2 m (40 ft) and peak fire heat release rates ranging from 150 kW to 3.8 MW. Use of this model with building geometries or fire characteristics other than those used in this evaluation may require further evaluation or testing.

9783030822958

10.1007/978-3-030-82295-8 doi


Detectores

TA165 / 2022 EB